SC(B) Epoxy Cast Resin Dry-Type Transformer

SC(B) Epoxy Cast Resin Dry-Type Transformer

F/H class insulation dry-type transformers with epoxy resin cast coils. Zero oil, zero pollution, ideal for indoor installations in commercial buildings, hospitals, data centers, and high-rise buildings. Compliant with IEC 60076-11.

Rated Voltage6kV, 10kV, 20kV, 35kV
Capacity Range30 – 2,500 kVA
Frequency50Hz / 60Hz
Cooling MethodAN (Natural Air) / AF (Forced Air)
Insulation ClassClass F (155°C) / Class H (180°C)
Core MaterialLow-loss grain-oriented silicon steel
HV WindingEpoxy resin vacuum cast coil
LV WindingCopper foil winding
No-load LossMeets IEC 60076-11 Level A₀
Load LossMeets IEC 60076-11 Level B₀
Impedance Voltage4% – 6%
Temperature RiseClass F ≤ 100K, Class H ≤ 125K
Protection RatingIP20 (standard), IP23/IP31 optional
Fire ResistanceSelf-extinguishing, Class E2 environment
Altitude≤ 1000m (derate above)
StandardsIEC 60076-11, GB/T 10228, IEEE C57.12.01
CertificationsISO 9001, CE, CNAS, UL (optional)

SC(B) Epoxy Cast Resin Dry-Type Transformer — Details

Overview

Our SC(B) series dry-type transformers use advanced vacuum pressure impregnation (VPI) and epoxy resin casting technology to deliver safe, reliable, and maintenance-free power transformation for indoor applications.

Key Features

  • Zero Oil, Zero Pollution: No flammable oil means no fire risk and no environmental contamination
  • Maintenance-Free: Epoxy cast resin coils resist moisture, dust, and corrosive environments
  • Low Noise: Optimized core clamping design achieves noise levels below 50dB
  • Self-Extinguishing: Class E2 environmental rating — safe for hospitals, schools, and underground installations
  • Compact Design: Smaller footprint than oil-immersed equivalents, ideal for space-constrained locations

Applications

  • Commercial buildings and shopping malls
  • Hospitals and healthcare facilities
  • Data centers and server rooms
  • Underground transport systems (metro, tunnels)
  • High-rise residential buildings
  • Clean room and semiconductor facilities

Temperature Monitoring

Optional intelligent temperature controller provides:

  • Real-time winding temperature display
  • Over-temperature alarm and trip protection
  • Automatic fan control (AF cooling mode)
  • RS485 communication for SCADA integration

Ready to Power Your Next Project?